What this tool does
Size DC cables in seconds. Enter current, round-trip length, system voltage, allowed % drop, and conductor material. The tool outputs the minimum cross-section (mm² and approx. AWG), plus actual voltage drop and power loss for the selected size.
Inputs
- Current (A)
- Round-trip length (m) (out + back)
- System voltage (V) — 12 / 24 / 48
- Max voltage drop (%) — e.g., 3–5% for branches
- Conductor — Copper or Aluminum
Outputs
- Min cable size — mm² and approx. AWG
- Voltage drop (V, % of system)
- Power loss (W) at the entered load
How to use
- Enter A, round-trip meters, system V, max % drop, and material.
- Read the minimum mm² / AWG and the resulting V drop / W loss.
- If near limits or in hot runs, choose the next size up.
Example
Inputs: 30 A, 8 m round-trip, 12 V, 3% max, Copper Result (approx.):
- Required ≥ 11.5 mm² → pick 16 mm² (≈ 5 AWG)
- V drop ≈ 0.26 V (≈ 2.16%)
- Loss ≈ 7.8 W
Notes & assumptions
- Uses typical resistivity at ~20 °C. Heat and bundling increase drop.
- Voltage-drop sizing doesn’t replace ampacity checks—always verify cable current rating and fusing.
- Round-trip length is there and back. Don’t forget return path in chassis-grounded systems.