What this tool does
Convert your daily energy use and days of autonomy into a required battery capacity (Ah) at your system voltage, then suggest a module count/config (S×P) for LiFePO₄ or AGM.
Inputs
- Daily use (Wh/day)
- Autonomy (days) you want off-grid
- Allowed DoD (%) — e.g., LiFePO₄ 80–90%, AGM ~50%
- System voltage (V) — 12 / 24 / 48
- Module specs (optional, for S×P): module voltage (V) and capacity (Ah)
Outputs
- Required capacity (Ah) at system voltage
- Suggested S×P using your module specs (e.g., 2P × 4S)
- Bank voltage & capacity preview (Ah @ V, Wh total)
Formula
Ah required = (Wh/day * days) / (System V * DoD_fraction) where DoD_fraction is 0–1 (e.g., 80% → 0.8)
How to use
- Enter Wh/day, autonomy (days), DoD%, and system V.
- Optionally add module V and module Ah to get a concrete S×P layout.
- Use the result to pick batteries (and sanity-check weight, charge rates, space).
Example
- Daily use: 1,200 Wh/day
- Autonomy: 2 days
- System: 12 V, DoD 80% (0.8)
- Required Ah = (1200 × 2) / (12 × 0.8) = 250 Ah
Module plan (if using 12 V, 100 Ah LiFePO₄ modules):
- Series needed to match 12 V: 1S
- Parallels to reach ≥250 Ah: 3P → 3 × 100 Ah = 300 Ah (headroom is good)
Notes & assumptions
- DoD% is the usable fraction. Higher DoD shrinks the required bank but may reduce longevity.
- LiFePO₄ tolerates higher DoD and cycles better than AGM. Charge profile differs.
- Always verify physical size, BMS limits, and charge/discharge current vs loads and chargers.